pdf-logo_002
View & Download PDF

VLT® AutomationDrive

The VLT® AutomationDrive is a single drive concept that covers an entire range of applications,
which is a major benefit in commissioning, operating and maintaining the equipment.

The modular open-technology platform that VLT® Automation Drive is built on makes it exceptionally adaptable and programmable. Its configurable, user-friendly interface supports local languages and letters.
Pluggable options
The drive solution can be adapted to any application due to the flexible option structure. Numerous options are available and can be mounted and tested from factory or be plugged in later for change-over or upgrade.
Automation_Drive_0001Adapts to the future
The modular concept of VLT® Auto-mation Drive makes it highly adaptable – also to future features and options.
Modularity offers the benefit of buying on a need-to-have basis without losing future possibilities.

Hot pluggable Control Panel
The Local Control Panel (LCP) can be plugged in directly or connected through a cable for remote commissioning.
The LCP can be disconnected during operation and replaced with a blind cover. Settings are easily transferred via the LCP from one drive to another or from a PC to a drive with the VLT® Set-up Software MCT 10.
Awarded
VLT® AutomationDrive has received the Frost & Sullivan award for innovation and the iF Design Award for its user-friendliness.
Power range
3 x 200 – 240 V …………………0.25 – 37 kW
3 x 380 – 480/500 V ……… 0.37 – 800 kW
3 x 525 – 600 V …………………0.75 – 75 kW
3 x 535 – 690 V ………………. 37 – 1200 kW
Normal overload …………… 45 – 1400 kW

Feature Benefit
Reliable Maximum uptime
Ambient temperature 50 C without derating o Less need for cooling or oversizing
Available in IP 00, 20, 21, 54, 55 and 66 enclosures Suitable for harsh and wash down areas
Resistant to wear and tear Low lifetime cost
Back-channel cooling for frame D, E and F Prolonged lifetime of electronics
User-friendly Saves commissioning and operating cost
Plug-and-Play technology Easy upgrade and change over
Awarded control panel User-friendly
Intuitive VLT® interface Saves time
Pluggable cage clamp connectors Easy connection
Exchangeable languages User-friendly
Intelligent
Intelligent warning systems Warning before controlled stop
Smart Logic Control Reduces need for PLC capacity
Advanced plug-in features Easy commissioning
Safe stop Safety cat. 3 (EN 954-1), PL d (ISO 13849-1),Stop cat. 0 (EN 60204-1)/td>
STO: Safe Torque Off (IEC 61800-5-2) SIL 2 (IEC 61508)
SIL CL 2 (IEC 62061)
Intelligent heat management Excess heat effectively removed
Options
The following options are available:
Fieldbus options
MCA 101 Profibus
MCA 104 DeviceNet
MCA 105 CanOpen
MCA 113 Profibus VLT® 3000 protocol converter
MCA 114 Profibus VLT® 5000 protocol converter
MCA 120 PROFINET
MCA 121 Ethernet IP
MCA 122 Modbus TCP
I/O and feedback options
MCB 101 General Purpose I/O
MCB 102 Encoder
MCB 103 Resolver
MCB 105 Relay
MCB 107 24 V input option for control voltage
MCB 113 Extended Relay Card
MCB 114 VLT® Sensor Input
Safety options
MCB 108 Safety PLC interface (DC/DC converter)
MCB 112 ATEX-PTC Thermistor Card

Brake chopper (IGBT) option
Connected to an external brake resistor, the built-in brake chopper limits the load on the intermediate circuit in the case the motor acts as a generator.

Specifications
Mains supply (L1, L2, L3)
Supply voltage 200 – 240 V ±10%
FC 301: 380 – 480 V ±10%
FC 302: 380 – 500 V ±10%, 525 – 600 V ±10%
525 – 690 V ±10%
Supply frequency 50/60 Hz
True Power Factor (λ) 0.92 nominal at rated load
Displacement Power Factor (cosф) near unity (>0.98)
Switching on input supply L1, L2, L3 Maximum 2 times/min.
Output data (U, V, W)
Output voltage 0 – 100% of supply voltage
Output frequency FC 301: 0.2 – 1000 Hz (0.25 – 75 kW)
FC 302: 0 – 1000 Hz (0.25 – 75 kW)
0 – 800 Hz (90 – 1200 kW)
0 – 300 Hz (Flux mode)
Switching on output Unlimited
Ramp times 1 – 3600 sec.

Note: 160% current can be provided for 1 minute. Higher overload rating is achieved by oversizing the drive.

Digital inputs
Programmable digital inputs FC 301: 4 (5) / FC 302: 4 (6)
Logic PNP or NPN
Voltage level 0 – 24 V DC

Note: One/two digital inputs can be programmed as digital output for FC 301/FC 302.

Analogue inputs
Analogue inputs 2
Modes Voltage or current
Voltage level FC 301: 0 to +10 V / FC 302: -10 to +10 V (scaleable)
Current level 0/4 – 20 mA (scaleable)
Pulse/encoder inputs
Programmable pulse/encoder inputs FC 301: 1 / FC 302: 2
Voltage level 0 – 24 V DC (PNP positive logic)
Digital output*
Programmable digital/pulse outputs FC 301: 1 / FC 302: 2
Voltage level at digital/frequency output 0 – 24 V
Analogue output*
Programmable analogue outputs 1
Current range 0/4 – 20 mA
Relay outputs*
Programmable relay outputs FC 301: 1 / FC 302: 2
Cable lengths
Max. motor cable lengths FC 301: 50 m / FC 302: 150 m (screened/armoured)
FC 301: 75 m / FC 302: 300 m (unscreened/unarmoured)

*More analogue and digital inputs/outputs can be added by options

Motion Control Options
MCO 305 Programmable Motion Controller
MCO 350 Synchronizing Controller
MCO 351 Positioning Controller
MCO 352 Center Winder ControllerPower options
Brake resistors
Sine-Wave Filters
dU/dt Filters
Harmonic Filters (AHF)Other accessories
IP 21/NEMA 1 Kit (convert IP 20 to IP 21)
PROFIBUS adapter
Sub-D9 Connector
Decoupling plate for fieldbus cables
USB connection cable to PC
Panel Through option
LCP panel mounting kit
Mains disconnect optionHigh power options
IEC Emergency stop with Safety Relay
Safety Stop with Safety Relay
RFI Filters
NAMUR terminals
RCD
IRM
Mains shielding
Regen terminals

Please see the VLT® High Power Drive Selection Guide for the complete range of options.