Pressure transmitter for air and water applications
Type MBS 1900
The pressure transmitter MBS 1900 is designed for use in air and water applications like Booster Pumps and Air Compressors. The semi-flexible pressure transmitter programme covers different output signals, absolute or gauge (relative) versions, measuring ranges from 0 – 4 bar to 0 – 25 bar and a wide range of pressure and electrical connections. Enclosure material is stainless steel AISI 316L.
Features
y Designed for use in air and water applications
y Wetted parts of stainless steel (AISI 304)
y Pressure ranges in relative (gauge) or absolute from 0 up to 25 bar
y Output signals: 4 – 20 mA, or ratio metric
y Absolute or relative (gauge) sensor element
y A wide range of pressure and electrical connections
y Digitally compensated
Approvals
UL Approval, Certificate number: E31024
Performance (EN 60770) | |
---|---|
Accuracy (@ 20 °C) (incl. non-linearity, hysteresis and repeatability) | ≤ ± 1.0% FS |
Non-linearity BFSL (conformity) | ≤ ± 0.5% FS |
Hysteresis and repeatability | ≤ ± 0.1% FS |
Total error band inside the compensated temperature range | ≤ ± 3.0% FS |
Response time | < 4 ms |
Overload pressure (Static) | 3 × FS (max. 75 bar) |
Burst pressure | 4 × FS (max. 100 bar) |
Durability, P: 10 – 90% FS | > 10 ×106 cycles |
Electrical specifications | ||
---|---|---|
Nom. output signal (short-circuit protected) | 4 − 20 mA | Ratiometric (10 – 90% of Vsupp.) |
Supply voltage [UB], polarity protected | 9 – 28 V | 5 V ± 10% |
Supply – current consumption | ≤ 5 mA | |
Supply voltage dependency | ≤ ± 0.1% FS / 10 V | ≤ ± 0.1% FS / 10 V |
Load [RL] (load connected to 0V ) | RL ≤ (UB -10V ) / 0.02A | RL ≥ 5 KΩ @ 5 V d.c. |
Output impedance | < 25 Ω |
Environmental conditions | |
---|---|
Sensor temperature range | 0 – 80 °C |
Max. media temperature | 110 – (0.35 × ambient temperature) |
Ambient temperature range (depending on electrical connection) | -20 – 80 °C |
Compensated temperature range | 0 – 80 °C |
Transport / Storage temperature range | -50 – 85 °C |
EMC – Emission | EN 61000-6-3 |
EMC – Immunity | EN 61000-6-2 |
Insulation resistance | > 100 MΩ at 500 V |
Vibration stability | Sinusoidal | 15 g, 5 Hz – 2 kHz | IEC 60068-2-6 |
Random | 7.5 g rms , 5 Hz – 1 kHz | IEC 60068-2-64 | |
Shock resistance | Shock | 200 g / 1 ms | IEC 60068-2-27 |
Free fall | 1 m | IEC 60068-2-32 | |
Enclosure (depending on electrical connection) | see page 4 |
Mechanical characteristics | ||
---|---|---|
Materials | Wetted parts | EN 10088-1; 1.4301 (AISI 304) |
Enclosure | EN 10088-1; 1.4404 (AISI 316 L) | |
Electrical connections | see page 4 | |
Net weight (depending on pressure connection and electrical connection) | 0.15 – 0.3 kg |
Mounting instructions | |
---|---|
Width across flats | 24 mm |
Mounting torque max | 20 Nm |
Ordering standard
Non-standard build-up combinations may be selected. However, minimum order quantities may apply. Please contact your local Danfoss office for further information or request on other versions.
Dimensions / Combinations